Foam System Design Calculator
Fixed foam discharge outlet count, application rate, and discharge time for tank fire protection (NFPA 11-2021 §5.2, §5.3)
◉ NFPA 11-2021 CHAPTER 5 STYLE CHECK · NOT A REGULATORY SUBMISSION TOOL
⚠ Indicative tool only. This source PDF is a pure scan with no text layer at all, so every table here was read directly from the page images, not extracted text. This is a different tool from the existing Fire Water Demand calculator (OISD-116/API RP 2021) — that one computes bulk cooling/foam water volume; this one sizes the foam chamber/outlet layout itself. They use different bases and aren't meant to be summed. Alcohol-resistant foam requirements for fixed discharge outlets (Table 5.2.5.3.4) were referenced by the standard but not independently verified here — consult that table directly if you're protecting water-soluble/polar-solvent contents with fixed outlets.
Identification
Research entries stay private to you for practice/testing. Switch to Official once this is a real design your company should see.
Tank Type & Units
Number of Fixed Foam Discharge Outlets (Table 5.2.5.2.1)
Result
Minimum number of discharge outlets
Discharge Rate & Time — Fixed Outlets (Table 5.2.5.2.2, Type II)
If your apparatus delivers more than the minimum rate, §5.2.5.2.3 permits a proportionate reduction in discharge time, down to a floor of 70% of the minimum time.
Result
Minimum application rate
Minimum discharge time
Adjusted discharge time (if higher rate used)
Alternative: Monitor / Handline Protection (Table 5.2.4.2.2)
Monitor nozzles may serve as primary protection for cone roof tanks under semi-fixed system conditions (§5.2.4.1.1). Handlines are not permitted as primary protection for tanks over 30 ft (9 m) diameter or 20 ft (6.1 m) height (§5.2.4.1.2).
Result (same hydrocarbon type as above)
Minimum application rate
Minimum discharge time
Handline eligibility (§5.2.4.1.2)
Save & Report